Input
|
Input System
|
Single Phase & earth ground
|
|
Rated Voltage
|
230VAC
|
|
Voltage Range
|
115V AC-300V AC
|
|
Frequency
|
50Hz
|
|
Power Factor
|
>0.99
|
|
Voltage range of bypass
|
(80+5) V AC(286+5) V AC
|
|
Output
|
Output System
|
Single Phase & earth ground
|
|
Wave Form
|
Pure Sine Wave
|
|
Rated voltage
|
230V AC
|
|
Power Factor
|
0.8
|
|
Voltage Precision
|
+2%
|
|
Output Frequency
|
Normal Mode
|
The output Frequency synchronizes with the input frequency
|
|
Battery Mode
|
The output frequency is 50Hz when the input frequency is not in the range of 45Hz-54Hz
|
|
Inverter overload capacity (Utility power, 25C)
|
105%+5%<Load<125%+5% 50s transfer to bypass
125%+5%<Load<150%+5% 25s transfer to bypass
Load>150%+5%, 300ms transfer to bypass
|
|
Transfer Time
|
0 ms(Normal mode-Battery mode)
|
|
<4ms(Normal mode-Bypass)
|
|
Crest Factor
|
3:1
|
|
Battery
|
Batteries Voltage
|
36V DC
|
72V DC
|
96V DC
|
240V DC
|
|
Battery Quantity
|
3
|
None
|
6
|
None
|
8
|
None
|
20
|
none
|
|
Battery Type
|
Sealed maintenance-free- lead-acid battery of battery voltage 12V/7AH
|
|
Backup Time(25 C)
|
Full load >5 min(standard)
|
|
Charge current
|
1A
|
7A
|
1A
|
7A
|
1A
|
7A
|
1A
|
7A
|
|
Mechanic
|
(WxHxD) mm
|
144x229x350
|
190x328x424
|
190x328x424
|
260x510x530
|
|
Weight(kg)
|
11.5
|
6
|
24
|
12
|
28
|
12
|
|
45
|
|
Environmental
|
Ambient Temperature
|
0C-40C
|
|
Environment humidity
|
20%-90%(No condensation)
|
|
Altitude
|
Lower than 1000m: no derating Over 1000m: 1% derating for every 100m rise
|
|
Storage temperature
|
15C-45C
|